Input for RTD, TC, mV, linear resistance, mA, and V
3.75 kVAC galvanic isolation
4…20 mA loop output
1- or 2-channel version
DIN rail mounting
Advanced features
The 5131A transmitter can be configured with the software program PReset using a standard PC and the Loop Link communications unit.
Application
Independent channel jumper selectable inputs for current/voltage or temperature.
Current input programmable in range 0…100 mA and voltage inputs in range 0…250 VDC.
Linearized, electronic temperature measurement with RTD or TC sensor.
Conversion of linear resistance variation to a standard analog current / voltage signal, for example from solenoids and butterfly valves or linear movements with attached potentiometer.
4- or 3-wire connection automatic cable compensation or 2-wire connection with programmable cable compensation.
Configurable sensor error detection including NAMUR NE43.
Technical characteristics
The 2-channel version has full galvanic isolation between the channels.
Separation of circuits in PELV/SELV installations.