Free Chlorine Analyzer, Aqua2000-FCL

Free Chlorine Analyzer, Aqua2000-FCL

The Aqua2000-FCL is a Free Chlorine Analyzer that automatically and continuously measures and transfers data of residual chlorine and pH in real time without the use of a reagent. The innovative design of this device makes it easy to check the sensor status while offering easy maintenance and a user-friendly interface. With pH and temperature compensation, the Aqua2000-FCL allows accurate measurement of residual chlorine in various environments.

  • reagent-free polarograph amperometric sensor
  • high-precision via gold cathode detector
  • electrode protection technology with membrane cap
  • low-maintenance, designed for long-term use (6 months)
  • easy to install and low cost of ownership
  • auto compensation for pH and water temperature

Description

This Free Chlorine Analyzer, the Aqua2000-FCL, automatically and continuously measures free chlorine, pH, and water temperature in real time by applying a reagent-free amperometric measurement method. This Water Quality Analyzer, from Bluesen, features a visible flow measurement structure. Its design allows operators to check the condition of the sensor and state of the measurement unit to provide accurate and stable water quality measurement data under varying conditions.

  • polarograph amperometric method (EPA 344.0, reagent free)
  • high-precision / sensitivity gold cathode detector
  • electrode protection technology with membrane cap
  • available for long-term use (6 months)
  • easy and affordable to maintain
  • auto compensation for pH and water temperature

Aqua2000-FCL Free Chlorine Analyzer

Bluesen-Aqua-2000-FCL-Free-Chlorine-Analyzer-Tap-Water-Analysis-Potable-Water-Analyzer-Process-Solutions-Texas

Physical Characteristics
  • Display: 4.3 inch TFT LCD touchscreen
  • Size (mm): 195(W) x 183(H) x 90(D)
  • Waterproof Rating: IP65
  • Power / Power Consumption: AC100/240V, 50/60Hz, 10W
  • Output: 4-20 mA, 2CH
  • Communication Options: RS232, RS485
  • Download Options: USB, SD card
Free Chlorine Measurement
  • Measurement Method: polarograph amperometric (reagent free sensor)
  • Electrode: gold cathode, silver anode (anodizing)
  • Structure: electrode protection by membrane cap
  • Measurement Type: pH and temperature auto compensation
  • Measurement Range: 0-2/10/20 mg/L (available to set the range)
Water Temperature
  • Measurement Range: PT1000Ω
  • Electrode Material: platinum thermometer (built in water quality sensor)
  • Measurement Range: -40 to 158˚F (-20 to 70˚C)