Configuration and monitoring by way of detachable display front (PR 45xx).
Selection of direct or inverted function for each channel via PR 45xx.
Advanced monitoring of internal communication and stored data.
Optional redundant supply via power rail and/ or separate supply.
SIL 2 functionality is optional and must be activated in a menu point.
Application
9202B can be mounted in the safe area or in zone 2 / Cl. 1 div. 2 and receive signals from zone 0, 1, 2, and zone 20, 21, 22 including mining / Class I/II/III, Div. 1, Gr. A-G.
Pulse isolator for transmission of signals to the safe area from NAMUR sensors and mechanical switches installed in the hazardous area.
Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
The 9202B has been designed, developed, and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
1 green and 2 yellow/red front LEDs indicate operation status and malfunction.
2.6 kVAC galvanic isolation between input, output, and supply.
Mounting
The devices can be mounted vertically or horizontally without distance between neighboring units.