Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
HART communication and 4…20 mA analog PV output for individual, difference or the average temperature measurement of up to two RTD or TC input sensors.
Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
Amplification of bipolar mV signals to standard 4…20 mA current signals.
Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.
Technical characteristics
HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
The HART 7 protocol offers:
∙ Long Tag numbers of up to 32 characters.
∙ Enhanced Burst Mode and Event notification with time stamping.
∙ Device variable and status mapping to any dynamic variable PV, SV, TV, or QV.
∙ Process signal trend measurement with logs and summary data.
∙ Automatic event notification with time stamps.
∙ Command aggregation for higher communication efficiency.
6337D is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
Continuous check of vital stored data.
Meeting the NAMUR NE 21 recommendations, the 6337D HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 6337D meets NAMUR NE43 and NE89 recommendations.
Mounting / installation
DIN rail mounting with up to 84 channels per meter.
Configuration via standard HART communication interfaces or by PR 5909 Loop Link.
The 6337D can be mounted in zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/ III, Division 1, Groups A, B, C, D.